3RV2011-0EA20

The 3RV2011-0EA20 is a Siemens SIRIUS S00 frame motor protection circuit breaker with a current adjustment range of 0.28~0.4 A, spring terminals, no built-in auxiliary switch (standard type), rated at 690V AC, and a maximum breaking capacity of 100kA. It is suitable for overload and short circuit protection of three-phase motor main circuits.

Share To
Product Positioning

The 3RV2011-0EA20 is a Siemens SIRIUS series S00 frame motor protection circuit breaker with a current adjustment range of 0.28~0.4 A. It is a standard version without auxiliary switches and is suitable as an overload and short circuit protection device for the main circuit of a three-phase motor.

Core Product Advantages and Features
Precise overload current adjustment
The current adjustment range is 0.28~0.4 A, and the set value can be finely adjusted according to the actual rated current of the motor, providing thermal overload protection for the appropriate load.
High short-circuit breaking capacity
With a short-circuit breaking capacity of up to 100kA (240/400/500V AC), it can reliably disconnect the circuit even in the event of a severe short-circuit fault.
S00 Miniaturized Frame Design
Adopting the SIRIUS S00 standard frame, it has a compact size and can be installed on a 35mm DIN rail for wiring, saving control panel space.
Terminal and auxiliary contact configuration
This is a standard version without auxiliary switches, with a simple structure and compact size, suitable for applications that only require protection of the main circuit.
project Specification
model 3RV2011-0EA20
Product Type SIRIUS motor protection circuit breaker (motor starting protector)
Frame size S00
Current adjustment range 0.28~0.4 A
Instantaneous short circuit trip value 5.2 A
Break away from level CLASS 10
Terminal type Spring-type terminals
Auxiliary switch None (Standard type)
Rated operating voltage 690V AC (Operating range 20~690V AC, 50/60Hz)
Extreme number 3-pole (three-phase main circuit)
Short circuit breaking capacity Maximum 100kA (240/400/500V AC)
Protection level IP20 (Front Panel and Terminals)
Installation method Screw-fixed or snap-fit mounted on a 35mm DIN rail (DIN EN 60715).
Operating temperature range -20°C ~ +60°C
Applicable Standards IEC 60529, DIN EN 60715