3RV2011-1DA15

The 3RV2011-1DA15 is a SIRIUS S00 frame three-pole motor protection circuit breaker with a current setting range of 2.2~3.2A, a rated insulation voltage of 690V, IP20 protection, and quick installation on a 35mm DIN rail. It is suitable for overload and short circuit protection of motor and electric motor circuits.

Share To
Product Positioning

The 3RV2011-1DA15 is a Siemens SIRIUS series S00 frame motor protection circuit breaker. It provides overload and short circuit protection within a current setting range of 2.2~3.2A with a thermal-magnetic tripping mechanism, and is suitable for use in small and medium-sized motor circuits such as pumps, fans, and conveyor belts.

Core Product Advantages and Features
Thermomagnetic Dual Trip Protection
Combining thermal overload protection and electromagnetic instantaneous short-circuit protection, a single component covers both fault modes, reducing the number of components in the distribution box.
S00 Small Frame Design
The SIRIUS S00 compact frame, with a width of only 45mm, effectively reduces the internal power distribution space of the control box and facilitates the side-by-side installation of multiple circuits.
35mm DIN rail quick installation
Supports standard 35mm DIN rail snap-on installation, enabling quick on-site construction and subsequent maintenance and replacement, reducing downtime.
Adjustable current setting knob
The panel current setting range is 2.2~3.2A, which can be finely adjusted according to the actual rated current of the motor to avoid malfunction or insufficient protection.
Clearly define the short-circuit instantaneous jump setting value
The short-circuit instantaneous trip (N-release) setting is 42A, which can be used in conjunction with upstream circuit breakers or fuses for selective protection.
project Specification
Product Category SIRIUS S00 frame motor protection circuit breaker
model 3RV2011-1DA15
Current setting range (CLASS 10) 2.2~3.2A
Short-circuit instantaneous jump setting (N-release) 42A
Terminal type Screw terminals, including 1 NO + 1 NC auxiliary contacts
Extreme number 3 poles
Rated operating voltage 20~690V AC
Rated insulation voltage 690V (Pollution Level 3)
Short-circuit breaking capacity Icu (240V/400V) 100kA
Short-circuit breaking capacity Icu (690V) 10kA
Protection level IP20 (front)
Installation method 35mm DIN rail snap-on mounting (DIN EN 60715)
external width 45mm
Applicable relevant standards IEC 60529, IEC 60068-2-27
External dimensions (height × depth) 106mm×97mm