3RV2031-4WA10

Siemens SIRIUS 3RV2031-4WA10, S2 housing, Class 10 trip rating, 42...52A overload adjustment, instantaneous trip 741A, basic standard model without built-in auxiliary contacts.

Share To
Product Positioning

The 3RV2031-4WA10 is a standard S2 frame motor protection circuit breaker with an overload range of 42...52A. It features Class 10 tripping characteristics, has no built-in auxiliary contacts, and is suitable for overload and short-circuit protection of general three-phase motor circuits.

Core Product Advantages and Features
Overload current adjustable from 42 to 52A
The rotary overload current setting corresponds to a motor rated current range of 42 to 52 amps.
Applicable motor capacity is approximately 45kW (400V).
Depending on the manufacturer's specifications, it can meet the protection requirements of three-phase motors with a power rating of approximately 45kW under 400V.
Transient short circuit trips 741A
When a short circuit occurs, the 741A trips instantaneously, quickly disconnecting the faulty circuit.
DIN rail or screw fixing
It can be installed using DIN rail quick-release or screw locking methods, offering high flexibility in the construction of the distribution box.
project Specification
Instantaneous short-circuit trip current (N-release) 741A
Overload adjustment current range (A-release) 42...52A
Break away from level Class 10
Built-in auxiliary contacts None (Standard type)
Short-circuit breaking capacity Icu 100kA(240V)/65kA(400V)/8kA(500V)/4kA(690V)
Frame size S2
Extreme number 3P
Rated insulation voltage AC 690V
Applicable power supply voltage range AC 20...690V
Terminal type Screw terminals
Available wire diameter 2x (1...35mm²) or 1x (1...50mm²)
Protection level IP20
External dimensions (height x width x depth) 140 x 55 x 149 mm