3RV2031-4XA10

Siemens SIRIUS 3RV2031-4XA10, S2 housing, Class 10 trip rating, 49...59A overload adjustment, instantaneous trip 845A, basic standard model without built-in auxiliary contacts.

Share To
Product Positioning

The 3RV2031-4XA10 is a standard S2 frame motor protection circuit breaker with an overload range of 49...59A. It features Class 10 tripping characteristics, has no built-in auxiliary contacts, and is suitable for basic overload and short-circuit protection in general motor circuits.

Core Product Advantages and Features
Overload current adjustable from 49 to 59A
The knob sets the overload trip current, corresponding to a motor rated current of 49 to 59 amps.
Class 10 standard escape characteristics
Suitable for motor loads during normal start-up times, providing stable and reliable overload protection.
Transient short circuit trips 845A
When a short circuit occurs, the 845A can trip instantaneously, quickly cutting off the faulty circuit.
Screw terminal wiring design
It uses standard screw terminals, making installation and future maintenance and replacement relatively simple.
project Specification
Instantaneous short-circuit trip current (N-release) 845A
Overload adjustment current range (A-release) 49...59A
Break away from level Class 10
Built-in auxiliary contacts None (Standard type)
Short-circuit breaking capacity Icu 100kA(240V)/65kA(400V)/8kA(500V)/4kA(690V)
Frame size S2
Extreme number 3P
Rated insulation voltage AC 690V
Applicable power supply voltage range AC 20...690V
Terminal type Screw terminals
Available wire diameter 2x (1...35mm²) or 1x (1...50mm²)
Protection level IP20
External dimensions (height x width x depth) 140 x 55 x 149 mm