3RV2142-4MA10

SIRIUS 3RV2142-4MA10, S3 case motor protection circuit breaker, current setting range 80-100A, with CLASS 10 tripping characteristic and 100kA short circuit breaking capacity, suitable for high-power three-phase motor circuit protection.

Share To
Product Positioning

The 3RV2142-4MA10 is a SIRIUS 3RV2 series S3 enclosure motor protection circuit breaker with a current setting range of 80-100A. It is suitable for overload and short circuit protection of large three-phase induction motors.

Core Product Advantages and Features
S3 High Current Housing
It adopts an S3 housing design and has a current setting range of 80-100A, which can meet the starting protection requirements of large-horsepower motor circuits.
High short-circuit breaking capacity
With a rated short-circuit breaking capacity of 100kA and an instantaneous short-circuit tripping current of 1300A, it provides reliable short-circuit protection.
CLASS 10 overload characteristics
Built-in CLASS 10 overload trip curve, meeting the needs of general motor start-up protection applications.
Screw terminal wiring
The screw terminal design facilitates wiring work during the construction and maintenance of the distribution panel.
project Specification
series SIRIUS 3RV2
Casing size S3
Current setting range 80–100 A
Rated current 100 A
Instantaneous short-circuit trip current 1300 A
Rated short-circuit breaking capacity 100 kA
Extreme number 3P
Break away from level CLASS 10
Enclosure protection rating IP20 (front of terminal)
Installation method 35mm DIN rail clip/screw fixing
External dimensions (height × width × depth) 165 × 90 × 176 mm
Wiring method Screw terminals
Product Functions Motor protection with overload relay function