3RW4422-3BC44

Standard wiring provides 29A and 15kW, while delta wiring can reach 50A and 22kW. The control circuit uses spring-loaded terminals, which speeds up wiring installation. The electrical specifications are the same as the screw-terminal models in the same series, only the wiring method differs.

Share To
Product Positioning

The 3RW4422-3BC44 is a soft starter model in the SIRIUS 3RW44 series with spring-loaded terminals for the control circuit. Its rated current is the same as the screw-terminal models in the same series, making it suitable for control panel applications that require quick wiring.

Core Product Advantages and Features
Spring-loaded terminal design
The control circuit uses spring-loaded (screwless) terminals, which can shorten wiring construction and maintenance time.
15kW standard wiring capacity
With standard wiring at 400V, it can drive a 15kW three-phase motor, suitable for small and medium-sized equipment.
Delta connection upgraded to 22kW
With the Inside-Delta wiring method, the driving power can be increased to 22kW.
Built-in bypass connection
After startup, the bypass is automatically switched on to reduce heat generation and save energy.
project Specification
model 3RW4422-3BC44
Product Category SIRIUS 3RW44 Miniature Three-Phase Soft Starter
Rated current (standard wiring, 40°C) 29 A
Rated current (delta connection, 40°C) 50 A
Rated power (400V, standard wiring) 15 kW
Rated power (400V, delta connection) 22 kW
Rated power (230V, standard wiring) 5.5 kW
Rated power (230V, delta connection) 15 kW
Rated voltage range 200~460 V AC (-15%/+10%)
Control voltage AC 230 V (50/60 Hz)
Enclosure protection rating IP20 front finger touch protection
Main circuit terminals Crimp terminal (box terminal)
Control circuit wiring terminals Spring-type terminals
External dimensions (width x height x depth) 170 x 192 x 270 mm