3UG4825-1CA40
The SIRIUS 3UG4825-1CA40, equipped with a 3UL23 current transformer, monitors residual (leakage) current, supports IO-Link communication, has a measurement range of 10mA to 43A, operates on 24V DC power, and provides two sets of delayed switching contacts.
Product Positioning
The 3UG4825-1CA40 is a digital residual current monitoring relay from the Siemens SIRIUS 3UG4 series. It requires an external 3UL23 current transformer and supports IO-Link communication, making it suitable for ground fault monitoring applications.
Core Product Advantages and Features
Residual current monitoring
Equipped with a 3UL23 current transformer, the measurement range is 10mA to 43A, and the adjustable trip value is 30mA to 40A.
IO-Link support
Built-in IO-Link interface (COM2, 38.4kBaud) facilitates data upload and remote monitoring.
Adjustable delay time
The action delay and jump delay are adjustable from 0 to 999.9 seconds, and it also has a shutdown hysteresis function.
Simplified casing
22.5mm standard width housing, DIN rail mounting, suitable for control panels with limited space.