3RT2026-1BB44

Based on the standard 24V DC coil, the 3RT2026-1BB44 upgrades the auxiliary contacts to 4 points (2NO+2NC). The AC-3 rated 25A/11kW/400V remains unchanged, making it suitable for control panel designs that require multiple sets of contacts, such as indicator light feedback and interlocking circuits.

Share To
Product Positioning

Based on the 24V DC coil in the same series, the 3RT2026-1BB44 upgrades the auxiliary contact configuration to 4 groups (2NO+2NC), doubling the number of usable contacts compared to the more common 1NO+1NC. When the control panel needs to provide multiple independent signals such as operation indication, fault alarm, and interlock circuit simultaneously, choosing this model can save the extra space and wiring required for external auxiliary contact sockets. It is a value-added model that Kensun Motors often recommends to machine integrators.

Core Product Advantages and Features
2NO+2NC four sets of auxiliary contacts
It has twice the number of contacts compared to the standard 1NO+1NC configuration, meeting multiple feedback/interlocking requirements.
24V DC standard coil
It is compatible with the output voltage of most PLCs and relays, and the wiring is simple and intuitive.
The AC-3 25A/11kW main circuit remains unchanged.
It shares the same main circuit specifications as other models in the same series, making selection and spare parts management simpler.
Detachable auxiliary contact module
The contact base can be removed and replaced individually for maintenance, reducing overall downtime and replacement costs.
project Specification
model 3RT2026-1BB44
AC-3 rated current 25 A
AC-3 Rated Power (400V) 11 kW
Extreme number 3P
Coil Specifications 24 V DC
auxiliary contacts 2 NO + 2 NC
Main circuit terminals Screw terminals
net weight Approximately 0.640 kg
Rated usage category AC-3 (Motor Start/Stop)
Insulation voltage (pollution level 3) 690 V
Rated impulse withstand voltage 6 kV
Frontal protection level IP20 (according to IEC 60529)
Mechanical life (typical value) 10 million cycles
Ambient operating temperature -25°C ~ +60°C
Applicable Standards IEC 60947-4-1 / IEC 60947-5-1
chassis code S0
Installation method 35mm DIN rail or panel locking